Finding 139

?

Heat from a table's mounting structure, not from a module: listed and drawn, never counted as a defect.

Hotspot

None

Warm spot on the mounting structure

Temperature difference
3.6 °C
Where
Table MODULES-0166, module 1
Cause
Mounting structure (suspected)
Next step
Field Check
Thermal close-up of finding 139
Thermal close-upColour range 31.8 °C to 38.2 °C
Photo of finding 139
PhotoFrom photo-033

Its modules

Table MODULES-0166: the filled module is module 1.

Close view
The whole table
Module 1, north endNorthModule 54, south end

Filled black: the modules this finding covers. Outlined: the rest of the table.

On the plant

Table MODULES-0166 is filled black and ringed.

Open the plan

Details

Number
139
Class
Hotspot
Severity
None
Temperature difference
3.6 °CHottest point minus the module's mean
Maximum
38.2 °C
Mean
34.6 °C
Minimum
31.8 °C
Cause
Mounting structure (suspected)
Next step
Field Check
Table
MODULES-0166
Modules
1/54 · 1 module
Demonstration position
40.56284380285529, -81.08656456678224Latitude and longitude after the plant was moved for this demonstration.
Seen in
1 thermal frame
Close-up cut from
frame-033
Photo cut from
photo-033
Thermal colour range
31.8 °C to 38.2 °C