Finding 169
?
Heat from a table's mounting structure, not from a module: listed and drawn, never counted as a defect.
Hotspot
None
Warm spot on the mounting structure
- Temperature difference
- 3.1 °C
- Where
- Table MODULES-0199, module 28
- Cause
- Mounting structure (suspected)
- Next step
- Field Check


Its modules
Table MODULES-0199: the filled module is module 28.
Module 1, north endNorthModule 54, south end
Filled black: the modules this finding covers. Outlined: the rest of the table.
On the plant
Details
- Number
- 169
- Class
- Hotspot
- Severity
- None
- Temperature difference
- 3.1 °CHottest point minus the module's mean
- Maximum
- 33.1 °C
- Mean
- 30.0 °C
- Minimum
- 26.4 °C
- Cause
- Mounting structure (suspected)
- Next step
- Field Check
- Table
- MODULES-0199
- Modules
- 28/54 · 1 module
- Demonstration position
- 40.56274468697679, -81.08568402913833Latitude and longitude after the plant was moved for this demonstration.
- Seen in
- 1 thermal frame
- Close-up cut from
- frame-043
- Photo cut from
- photo-043
- Thermal colour range
- 26.4 °C to 33.1 °C
Left and right arrow keys move to the previous and next finding.