Finding 79

?

Heat from a table's mounting structure, not from a module: listed and drawn, never counted as a defect.

Hotspot

None

Warm spot on the mounting structure

Temperature difference
2.3 °C
Where
Table MODULES-0131, module 2
Cause
Mounting structure (suspected)
Next step
Field Check
Thermal close-up of finding 79
Thermal close-upColour range 36.5 °C to 39.8 °C
Photo of finding 79
PhotoFrom photo-020

Its modules

Table MODULES-0131: the filled module is module 2.

Close view
The whole table
Module 1, north endNorthModule 54, south end

Filled black: the modules this finding covers. Outlined: the rest of the table.

On the plant

Table MODULES-0131 is filled black and ringed.

Open the plan

Details

Number
79
Class
Hotspot
Severity
None
Temperature difference
2.3 °CHottest point minus the module's mean
Maximum
39.8 °C
Mean
37.5 °C
Minimum
36.5 °C
Cause
Mounting structure (suspected)
Next step
Field Check
Table
MODULES-0131
Modules
2/54 · 1 module
Demonstration position
40.562623519454796, -81.08756673992075Latitude and longitude after the plant was moved for this demonstration.
Seen in
1 thermal frame
Close-up cut from
frame-020
Photo cut from
photo-020
Thermal colour range
36.5 °C to 39.8 °C