Finding 114

?

Heat from a table's mounting structure, not from a module: listed and drawn, never counted as a defect.

Hotspot

None

Warm spot on the mounting structure

Temperature difference
6.8 °C
Where
Table MODULES-0050, module 28
Cause
Mounting structure (suspected)
Next step
Field Check
Thermal close-up of finding 114
Thermal close-upColour range 30.2 °C to 39.9 °C
Photo of finding 114
PhotoFrom photo-030

Its modules

Table MODULES-0050: the filled module is module 28.

Close view
The whole table
Module 1, north endNorthModule 54, south end

Filled black: the modules this finding covers. Outlined: the rest of the table.

On the plant

Table MODULES-0050 is filled black and ringed.

Open the plan

Details

Number
114
Class
Hotspot
Severity
None
Temperature difference
6.8 °CHottest point minus the module's mean
Maximum
39.9 °C
Mean
33.1 °C
Minimum
30.2 °C
Cause
Mounting structure (suspected)
Next step
Field Check
Table
MODULES-0050
Modules
28/54 · 1 module
Demonstration position
40.563039744408776, -81.08709099478212Latitude and longitude after the plant was moved for this demonstration.
Seen in
2 thermal frames
Close-up cut from
frame-030
Photo cut from
photo-030
Thermal colour range
30.2 °C to 39.9 °C