Finding 115

?

Heat from a table's mounting structure, not from a module: listed and drawn, never counted as a defect.

Hotspot

None

Warm spot on the mounting structure

Temperature difference
2.5 °C
Where
Table MODULES-0148, module 1
Cause
Mounting structure (suspected)
Next step
Field Check
Thermal close-up of finding 115
Thermal close-upColour range 34.4 °C to 39.2 °C
Photo of finding 115
PhotoFrom photo-022

Its modules

Table MODULES-0148: the filled module is module 1.

Close view
The whole table
Module 1, north endNorthModule 54, south end

Filled black: the modules this finding covers. Outlined: the rest of the table.

On the plant

Table MODULES-0148 is filled black and ringed.

Open the plan

Details

Number
115
Class
Hotspot
Severity
None
Temperature difference
2.5 °CHottest point minus the module's mean
Maximum
39.2 °C
Mean
36.7 °C
Minimum
34.4 °C
Cause
Mounting structure (suspected)
Next step
Field Check
Table
MODULES-0148
Modules
1/54 · 1 module
Demonstration position
40.562732659379606, -81.08709506632974Latitude and longitude after the plant was moved for this demonstration.
Seen in
1 thermal frame
Close-up cut from
frame-022
Photo cut from
photo-022
Thermal colour range
34.4 °C to 39.2 °C